| ID |
CVE-2026-3611
|
| Sažetak |
The Honeywell IQ4x building management controller, exposes its full web-based HMI without authentication in its factory-default configuration. With no user module configured, security is disabled by design and the system operates under a System Guest (level 100) context, granting read/write privileges to any party able to reach the HTTP interface. Authentication controls are only enforced after a web user is created via U.htm, which dynamically enables the user module. Because this function is accessible prior to authentication, a remote user can create a new account with administrative read/write permissions enabling the user module and imposing authentication under attacker-controlled credentials. This action can effectively lock legitimate operators out of local and web-based configuration and administration. |
| Reference |
|
| CVSS |
| Base: | 10.0 |
| Impact: | 6.0 |
| Exploitability: | 3.9 |
|
| Pristup |
| Vektor | Složenost | Autentikacija |
| NETWORK |
LOW |
NONE |
|
| Impact |
| Povjerljivost | Cjelovitost | Dostupnost |
| HIGH |
HIGH |
HIGH |
|
| CVSS vektor |
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:H/I:H/A:H |
| Zadnje važnije ažuriranje |
13-03-2026 - 20:06 |
| Objavljeno |
12-03-2026 - 21:16 |