ID |
CVE-2022-2502
|
Sažetak |
A vulnerability exists in the HCI IEC 60870-5-104 function included in certain versions of the RTU500 series product. The vulnerability can only be exploited, if the HCI 60870-5-104 is configured with support for IEC 62351-5 and the CMU contains the license feature ‘Advanced security’ which must be ordered separately. If these preconditions are fulfilled, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the targeted RTU500 CMU to reboot. The vulnerability is caused by a missing input data validation which eventually if exploited causes an internal buffer to overflow in the HCI IEC 60870-5-104 function. |
Reference |
|
CVSS |
Base: | 7.5 |
Impact: | 3.6 |
Exploitability: | 3.9 |
|
Pristup |
Vektor | Složenost | Autentikacija |
NETWORK |
LOW |
NONE |
|
Impact |
Povjerljivost | Cjelovitost | Dostupnost |
NONE |
NONE |
HIGH |
|
CVSS vektor |
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H |
Zadnje važnije ažuriranje |
25-09-2024 - 01:15 |
Objavljeno |
26-07-2023 - 06:15 |